How Siemens Touch Screen Enters Main Interface Automatically

Publish Date 2018-07-24
How Siemens Touch Screen Enters Main Interface Automatically
、1. To create a screen, users need to create two pictures for Siemens touch screen through Siemens programming software WinCC Flexible 2008, and configure the two pictures. Final completion of screen 1 and screen 2 programming configuration work;
2. Establish variables in variables of Siemens programming software WinCC Flexible 2008, establish internal variable Tag1, variable type is integer;
3. Creating screen events in user-created screen 1, select "event" - > "loading", select "SimulateTag" function in the function, and add variable Tag1 in the attribute of the function, select the appropriate time in the cycle, in which period 1 represents 200 ms;
4. Set variable events in the attributes of variable Tag1, select "event" - > "change the value", select "Activate Screen" in the function, and select "screen 2" in "screen name";
5. The simulation test user first takes screen 1 as the starting screen. After the simulation run, screen 1 appears first in the computer, and then automatically jumps to screen 2 after the time set by the user. The test is successful.
How to set the password of Siemens Touch Screen Jump Page:
1. In the left directory tree, select "User" under "Running System User Management". Establish user name and password, and select user rights, whether it is "administrator" or "operator". 2. Configure the user's login button in the screen. Use the "button" tool to define the "click" function in "event" and select "Show Logon Dialog".